4.7 Article

Optimal PMU Placement by an Equivalent Linear Formulation for Exhaustive Search

期刊

IEEE TRANSACTIONS ON SMART GRID
卷 3, 期 1, 页码 174-182

出版社

IEEE-INST ELECTRICAL ELECTRONICS ENGINEERS INC
DOI: 10.1109/TSG.2011.2167163

关键词

Integer linear programming; observability; optimal PMU placement (OPP); phasor measurement unit (PMU)

向作者/读者索取更多资源

Observability of bulk power transmission network by means of minimum number of phasor measurement units (PMUs), with the aid of the network topology, is a great challenge. This paper presents a novel equivalent integer linear programming method (EILPM) for the exhaustive search-based PMU placement. The state estimation implemented based on such a placement is completely linear, thereby eliminating drawbacks of the conventional SCADA-based state estimation. Additional constraints for observability preservation following single PMU or line outages can easily be implemented in the proposed EILPM. Furthermore, the limitation of communication channels is dealt with by translation of nonlinear terms into linear ones. Optimal PMU placement is carried out on the IEEE 118-bus test system in different scenarios. The comparison between obtained results of EILPM and those of other methods reveals optimality of the solutions. Moreover, the proposed method is successfully applied on the Iranian National Grid, which demonstrates it can effectively be employed for practical power networks.

作者

我是这篇论文的作者
点击您的名字以认领此论文并将其添加到您的个人资料中。

评论

主要评分

4.7
评分不足

次要评分

新颖性
-
重要性
-
科学严谨性
-
评价这篇论文

推荐

暂无数据
暂无数据