4.7 Article

A Simple Adaptive Overcurrent Protection of Distribution Systems With Distributed Generation

期刊

IEEE TRANSACTIONS ON SMART GRID
卷 2, 期 3, 页码 428-437

出版社

IEEE-INST ELECTRICAL ELECTRONICS ENGINEERS INC
DOI: 10.1109/TSG.2011.2149550

关键词

Adaptive protection; distributed generation; islanding; time overcurrent protection

资金

  1. PSO program [2006-1-6316]

向作者/读者索取更多资源

A significant increase in the penetration of distributed generation has resulted in a possibility of operating distribution systems with distributed generation in islanded mode. However, overcurrent protection of an islanded distribution system is still an issue due to the difference in fault current when the distribution system is connected to the grid and when it is islanded. This paper proposes the use of adaptive protection, using local information, to overcome the challenges of the overcurrent protection in distribution systems with distributed generation. The trip characteristics of the relays are updated by detecting operating states ( grid connected or island) and the faulted section. The paper also proposes faulted section detection using time overcurrent characteristics of the protective relays. Simulation results show that the operating state and faulted section can be correctly identified and the protection system settings can be updated to clear the faults faster.