4.3 Article

Experimental investigation of the influence of the air jet trajectory on convective heat transfer in buildings equipped with air-based and radiant cooling systems

期刊

出版社

TAYLOR & FRANCIS LTD
DOI: 10.1080/19401493.2014.938121

关键词

convective heat transfer coefficient; cooling; radiant wall; active chilled beam; air jet trajectory; Archimedes number

资金

  1. Danish Agency for Science, Technology and Innovation
  2. Ministry of Science and Technology of P.R. China (Danish International DSF) [09-71598, 2010DFA62410]

向作者/读者索取更多资源

The complexity and diversity of airflow in buildings make the accurate definition of convective heat transfer coefficients (CHTCs) difficult. In a full-scale test facility, the convective heat transfer of two cooling systems (active chilled beam and radiant wall) has been investigated under steady-state and dynamic conditions. With the air-based cooling system, a dependency of the convective heat transfer on the air jet trajectory has been observed. New correlations have been developed, introducing a modified Archimedes number to account for the air flow pattern. The accuracy of the new correlations has been evaluated to +/- 15%. Besides the study with an air-based cooling system, the convective heat transfer with a radiant cooling system has also been investigated. The convective flow at the activated surface is mainly driven by natural convection. For other surfaces, the complexity of the flow and the large uncertainty on the CHTCs make the validation of existing correlations difficult.

作者

我是这篇论文的作者
点击您的名字以认领此论文并将其添加到您的个人资料中。

评论

主要评分

4.3
评分不足

次要评分

新颖性
-
重要性
-
科学严谨性
-
评价这篇论文

推荐

暂无数据
暂无数据