4.6 Article

Ultra clean ventilation system performance relating to airborne infections in operating theatres using CFD modelling

期刊

BUILDING SIMULATION
卷 7, 期 3, 页码 277-287

出版社

TSINGHUA UNIV PRESS
DOI: 10.1007/s12273-013-0145-4

关键词

operating theatre; airborne infection; ventilation; CFD

资金

  1. European Union

向作者/读者索取更多资源

Preventing airborne infections during a surgical procedure is of paramount importance for effective and economical delivery of care, as well as for health and well-being of patients. Ultra clean ventilation (UCV) systems are commonly used in operating theatres, in particular for orthopaedic surgery because of the higher risk of infection from exposed deep wounds. This research, investigates the airflow pattern of a UCV based operating theatre using computational fluid dynamics (CFD). The effects of the opening and closing of doors in two pressurisation scenarios (0 and 20 Pa) with the surrounding spaces at various inlet and door inflow velocities are investigated. The UCV system operates effectively in the positive pressure (20 Pa) scenario but fails when there is no pressure difference between the operating theatre and surrounding areas. The implications of the research findings are discussed in the context of design guidance and the operation of the airflow system.

作者

我是这篇论文的作者
点击您的名字以认领此论文并将其添加到您的个人资料中。

评论

主要评分

4.6
评分不足

次要评分

新颖性
-
重要性
-
科学严谨性
-
评价这篇论文

推荐

暂无数据
暂无数据