4.3 Article

A developed energy management strategy for a stand-alone hybrid power system for medium rural health building

出版社

WILEY
DOI: 10.1002/etep.2103

关键词

load side management; hybrid energy system; health building; load profile; air conditioning system; environmental merits

向作者/读者索取更多资源

This paper deals with load side management strategy for (photovoltaic-wind-diesel) hybrid system for medium rural health building located in the Sahara region. The paper presents an overview about geographic and climate data of the location and develops a typical load profile of electrical energy, depending on a real investigation of daily electricity consumption. The base of the proposed management strategy is the control of the air conditioning system and the non-critical lighting of the building as they consume more than 50% of the total power consumption. The result shows that the reduction in the peak consumption is about 20% using the proposed management strategy, which has significant economical, technical, and environmental benefits. Copyright (C) 2015 John Wiley & Sons, Ltd.

作者

我是这篇论文的作者
点击您的名字以认领此论文并将其添加到您的个人资料中。

评论

主要评分

4.3
评分不足

次要评分

新颖性
-
重要性
-
科学严谨性
-
评价这篇论文

推荐

暂无数据
暂无数据