4.7 Article

An Adaptive PMU-Based Wide Area Backup Protection Scheme for Power Transmission Lines

期刊

IEEE TRANSACTIONS ON SMART GRID
卷 6, 期 3, 页码 1550-1559

出版社

IEEE-INST ELECTRICAL ELECTRONICS ENGINEERS INC
DOI: 10.1109/TSG.2014.2387392

关键词

Backup protection zone (BPZ); phasor measurement unit (PMU); smart transmission grid; wide area backup protection; wide area measurement system (WAMS)

向作者/读者索取更多资源

This paper proposes a novel adaptive wide area backup protection scheme for transmission lines. In the proposed scheme, both the faulted line and fault location are determined by a limited number of synchronized phasor measurements. Based on phasor measurement unit placement and network topology, subsets of lines and buses called backup protection zones (BPZs) are formed. After a fault occurs in the transmission network, the sum of zero- and/or positive-sequence currents entering the faulted BPZ highly increases, and hence, the faulted BPZ can be determined. The linear least squares method is then used to determine the faulted line, as well as the fault location by voltage and current phasors of the faulted BPZ. Accordingly, the proposed scheme provides a closed-form and noniterative solution for the faulted line and fault location identification problem. On the other hand, it readily determines the faulted line regardless of the fault type, fault resistance, and measurement errors. To show the effectiveness of the method, it is applied to the WSCC 9-bus and IEEE 118-bus test systems. Simulation results verify successful identification of the faulted BPZ as well as the faulted line within the faulted BPZ with limited measurement points.

作者

我是这篇论文的作者
点击您的名字以认领此论文并将其添加到您的个人资料中。

评论

主要评分

4.7
评分不足

次要评分

新颖性
-
重要性
-
科学严谨性
-
评价这篇论文

推荐

暂无数据
暂无数据