4.7 Article

An Integrated Model to Evaluate Losses in Water Distribution Systems

期刊

WATER RESOURCES MANAGEMENT
卷 23, 期 3, 页码 477-492

出版社

SPRINGER
DOI: 10.1007/s11269-008-9284-2

关键词

Water distribution networks; Non revenue water; Leakage; Pressure; Minimum night flow; EPANET; GIS

向作者/读者索取更多资源

To evaluate non revenue water (NRW) and losses in water distribution networks a methodology is developed by applying annual water balance and minimum night flow analyses. In this approach the main NRW components such as leakage from reported and un-reported bursts and background leakage, with real or estimated data, enabling assessment of indices of leakage performance are evaluated. Also, a novel procedure is introduced in this paper that can determine the nodal and pipe leakage by using a hydraulic simulation model. Recognising the pressure dependency of leakage the total consumption is divided into two parts, one pressure dependent and the other independent of local pressure, and the hydraulic behaviour of the network is analyzed. A computer code is developed to evaluate all components of water losses based on the proposed methodology. For better representation of the results and management of the system, the outputs are exported to a GIS model. Using the capabilities of this GIS model, the network map and attribute data are linked and factors affecting network leakage are identified. In addition, the effects of pressure reduction are investigated. The model is illustrated by a real case study. The results show that the suggested model has overcome the shortcomings of the existing methodologies by accounting for the leakage and other NRW components in water distribution networks more realistically.

作者

我是这篇论文的作者
点击您的名字以认领此论文并将其添加到您的个人资料中。

评论

主要评分

4.7
评分不足

次要评分

新颖性
-
重要性
-
科学严谨性
-
评价这篇论文

推荐

暂无数据
暂无数据