4.6 Article

Advanced performance of an open desiccant cycle with internal evaporative cooling

期刊

SOLAR ENERGY
卷 104, 期 -, 页码 103-114

出版社

PERGAMON-ELSEVIER SCIENCE LTD
DOI: 10.1016/j.solener.2013.07.022

关键词

Desiccant; Adsorption; Cooled sorption; Sorptive coated heat exchanger

资金

  1. German Federal Ministry of Economics and Technology [0327406A]
  2. Reiner Lemoine Stiftung for the Ph.D. research of Constanze Bongs

向作者/读者索取更多资源

An enhanced evaporatively cooled open sorption cycle which can be driven by solar thermal heat is presented as an environmentally benign alternative to conventional air conditioning cycles. Experimental data of the core component - the desiccant coated heat exchanger cooled by water evaporation are given. This evaporation of water in the heat exchanger leads to an increase in adsorbed water mass by 46% and an enhancement of the cooling capacity by factor 4.1 when compared to a solely air cooled process. By simulation analysis, the recently designed heat exchanger is then compared to data of an air cooled open sorption process published in earlier research. Measurement data of this earlier research are analysed with a dynamic model. It is demonstrated that only a fraction of the dry desiccant mass was actively cycled in the earlier prototype. Simulation of the evaporatively cooled current prototype underlines the enhanced performance that can be achieved with the new concept and prototype design. (C) 2013 Elsevier Ltd. All rights reserved.

作者

我是这篇论文的作者
点击您的名字以认领此论文并将其添加到您的个人资料中。

评论

主要评分

4.6
评分不足

次要评分

新颖性
-
重要性
-
科学严谨性
-
评价这篇论文

推荐

暂无数据