4.7 Article

On the estimation of thermal resistance in borehole thermal conductivity test

期刊

RENEWABLE ENERGY
卷 33, 期 11, 页码 2407-2415

出版社

PERGAMON-ELSEVIER SCIENCE LTD
DOI: 10.1016/j.renene.2008.01.021

关键词

GLHE standard sizing; line-source model; 3D numerical borehole model; p-linear average; thermal response test; thermal parameter estimation

向作者/读者索取更多资源

Sizing of ground-coupled loop heat exchangers (GLHE) depends on the ground thermal conductivity and capacity, and the borehole thermal resistance. One popular method to estimate the thermal parameters is the interpretation of in situ thermal response tests. Tile modeled response is T = (Tin + T..,)12, the average temperature of the fluid entering and leaving the ground. The Tn, response corresponds to the physically unrealistic hypothesis of constant heat flux along a borehole. Using a 3D finite element model of the borehole, we show that Tn, does not correspond to the fluid mean temperature within the borehole. Accordingly, with Tn,, an overestimation of the borehole thermal resistance results. The resistance overestimation has a noticeable economic impact. We propose instead a new estimator we name p-linear average of Tin and 7',,,, with parameter p --- > -1, as determined by numerical simulations. We show that the p-linear average closely fits tile average fluid temperature computed with the numerical model, hence avoiding bias in estimation of borehole thermal resistance. Finally, we discuss the problem of collinearity arising in tile estimation of thermal parameters. (c) 2008 Elsevier Ltd. All rights reserved.

作者

我是这篇论文的作者
点击您的名字以认领此论文并将其添加到您的个人资料中。

评论

主要评分

4.7
评分不足

次要评分

新颖性
-
重要性
-
科学严谨性
-
评价这篇论文

推荐

暂无数据
暂无数据