4.4 Article

Reducing the core loss of amorphous cores for distribution transformers

期刊

出版社

ELSEVIER SCIENCE INC
DOI: 10.1016/j.pnsc.2012.04.005

关键词

Amorphous core; Annealing technique; Reducing core loss; Loss deterioration; Distribution transformer

资金

  1. National High-Tech Research and Development Programme [2012AA030301]

向作者/读者索取更多资源

Although amorphous alloy ribbons have lower core loss, serious loss deterioration occurs in amorphous cores constructed from amorphous alloy ribbon for distribution transformer. In the present study, the loss deterioration mechanism and influencing factors of amorphous cores for distribution transformers were investigated. The influence of distributed gaps on core loss of transformer core was calculated by simulation software and validated by experiments. The boron fluctuation of amorphous alloy ribbons affects the annealing temperature of amorphous transformer cores. A superior core annealing technique with annealing parameters was developed, and appreciable decrease in core loss was obtained. (C) 2012. Chinese Materials Research Society. Production and hosting by Elsevier Ltd. All rights reserved.

作者

我是这篇论文的作者
点击您的名字以认领此论文并将其添加到您的个人资料中。

评论

主要评分

4.4
评分不足

次要评分

新颖性
-
重要性
-
科学严谨性
-
评价这篇论文

推荐

暂无数据
暂无数据