An integrated evaluation study of the ventilation rate, the exposure and the indoor air quality in naturally ventilated classrooms in the Mediterranean region during spring

期刊

SCIENCE OF THE TOTAL ENVIRONMENT
卷 502, 期 -, 页码 557-570

出版社

ELSEVIER
DOI: 10.1016/j.scitotenv.2014.09.060

关键词

IAQ; PM; CO2; Ventilation; Health; Naturally ventilated schools

资金

  1. European Union (European Social Fund-ESF)
  2. Greek national funds through the Operational Program 'Education and Lifelong Learning' of the National Strategic Reference Framework (NSRF)-Research Funding Program: Heracleitus II [MIS 346942]

向作者/读者索取更多资源

Ventilation rates and indoor air pollutants have been extensively monitored in nine naturally ventilated primary schools of Athens, Greece during spring. The ventilation rates and pollutant levels were studied during the teaching and non-teaching periods and ventilation profiles were created for each of the schools. The median ventilation rates per school ranged between 0.7 and 8 ACH while the average ventilation rate in all schools (11.7 l/s/p) was greater than the minimum recommended rates by ASHRAE for school classrooms. The average carbon dioxide (CO2) concentrations per school varied between 893 and 2082 ppm, while the majority of the cases were slightly above the recommended limit values. CO2 concentrations were also positively correlated to the number of students and negatively correlated to the ventilation rates. Particles of several size ranges (PM10, PM5, PM2.5, PM1, PM0.5 and UFP) were also measured and analyzed. PM10 concentrations exceeded the recommended limit values by more than 10 times for the majority of the cases. There were also many cases that the PM2.5 concentrations exceeded their limit values. PM concentrations were significantly affected by the ventilation rates and the presence of students. All of the measured particle sizes were greater during teaching than the non-teaching hours. For most of the cases the indoor to outdoor (I/O) concentrations ratios of PM10 and PM2.5 were much greater than one, indicating that the indoor environment was being mostly affected by indoor sources instead of the outdoor air. Furthermore it was found that chalk and marker boards' usage significantly affect indoor pollutant concentrations. Overall, the measured levels of exposure were for most of the cases greater than the recommended guideline values due to the intense presence of indoor pollution sources, even though the ventilation rates were in general satisfactory. (C) 2014 Elsevier B.V. All rights reserved.

作者

我是这篇论文的作者
点击您的名字以认领此论文并将其添加到您的个人资料中。

评论

主要评分

4.7
评分不足

次要评分

新颖性
-
重要性
-
科学严谨性
-
评价这篇论文

推荐

暂无数据
暂无数据