4.7 Article

Formaldehyde removal from air during membrane air humidification evaporative cooling: Effects of contactor design and operating conditions

期刊

JOURNAL OF MEMBRANE SCIENCE
卷 354, 期 1-2, 页码 55-62

出版社

ELSEVIER SCIENCE BV
DOI: 10.1016/j.memsci.2010.02.075

关键词

Evaporative cooling; Air humidification; Membrane contactor; Formaldehyde removal

资金

  1. University of Texas at San Antonio Faculty Research Award Program

向作者/读者索取更多资源

Counter-current parallel flow membrane contactors were studied to estimate likely formaldehyde removal rates from air occurring during membrane air humidification and evaporative cooling applications. A mathematical model and experimental measurements of formaldehyde removal are presented to assess the impact of possible operating conditions and contactor configurations on expected formaldehyde removal rates. Removal efficiencies were predominately controlled by shell side mass transfer coefficients. However, removals decrease when water velocity within the fiber lumens is low and water supplied to the modules approach module evaporative losses. While removal rates were found to be adequate to control formaldehyde emissions in most space air-conditioning applications, large volumes of water usage appear to be necessary. (C) 2010 Elsevier B.V. All rights reserved.

作者

我是这篇论文的作者
点击您的名字以认领此论文并将其添加到您的个人资料中。

评论

主要评分

4.7
评分不足

次要评分

新颖性
-
重要性
-
科学严谨性
-
评价这篇论文

推荐

暂无数据
暂无数据