4.8 Article

Optimal exergy control of building HVAC system

期刊

APPLIED ENERGY
卷 156, 期 -, 页码 555-565

出版社

ELSEVIER SCI LTD
DOI: 10.1016/j.apenergy.2015.07.051

关键词

Exergy; Model predictive control; HVAC; Exergy-based control

向作者/读者索取更多资源

Exergy or availability is an accurate metric related to quality of energy and it is used to determine sustainability of an energy system. Exergy has been extensively used to evaluate efficiency of energy systems and energy conversion processes. An exergy model for a building is presented in this study. In this paper, exergy destruction, which indicates the loss of work potential, is formulated as a function of physical parameters of the building model and environment. To minimize exergy destruction in an Heating, Ventilation and Air-Conditioning (HVAC) system, we develop model predictive control (MPC) technique using the exergy model. Comparing to a traditional on-off controller for the building, the proposed exergy-based MPC (XMPC) reduces the exergy destruction and energy consumption up to 22% and 36%, respectively. Simulation results also indicate the advantage of XMPC over conventional energy-based MPC (EMPC). The results show that XMPC reduces exergy destruction by 4% compared to EMPC as well as saving 12% more energy. (C) 2015 Elsevier Ltd. All rights reserved.

作者

我是这篇论文的作者
点击您的名字以认领此论文并将其添加到您的个人资料中。

评论

主要评分

4.8
评分不足

次要评分

新颖性
-
重要性
-
科学严谨性
-
评价这篇论文

推荐

暂无数据
暂无数据