4.8 Article

Thermal performance of a radiant floor heating system with different heat storage materials and heating pipes

期刊

APPLIED ENERGY
卷 138, 期 -, 页码 648-660

出版社

ELSEVIER SCI LTD
DOI: 10.1016/j.apenergy.2014.10.058

关键词

Experiment; Radiant floor heating; Phase change material; Capillary mat; Polyethylene coil; Heat storage

资金

  1. Fundamental Research Funds for the Central Universities [2014ZD08]
  2. Opening Funds of State Key Laboratory of Building Safety and Built Environment [BSBE2010-01]

向作者/读者索取更多资源

Experiments were carried out to investigate the performance of a low-temperature radiant floor heating system with different heat storage materials (sand and phase change material) and heating pipes (polyethylene coils and capillary mat) in the floor structure of a test room. Detailed temperatures in both floor structural layers and the air of the room were measured for four different combinations of these thermal mass and heating pipes during charge and discharge operations. The results showed that the floor structure with capillary mat provides more uniform temperature profile in vertical direction of the test room and needs much shorter time (nearly half) to attain the same room temperature than the cases with polyethylene (PE) coils during the charging process. Also, after the heat source was closed, the floor structures using phase change material (PCM) as thermal mass release heat about 2 times longer than the cases using sand. A CFD simulation is also performed which confirms the measured data during the charging and discharging processes. The results indicate the advantages of using PCM - capillary mat combination for low - temperature floor panel typical of solar - hot - water heating system. (C) 2014 Elsevier Ltd. All rights reserved.

作者

我是这篇论文的作者
点击您的名字以认领此论文并将其添加到您的个人资料中。

评论

主要评分

4.8
评分不足

次要评分

新颖性
-
重要性
-
科学严谨性
-
评价这篇论文

推荐

暂无数据
暂无数据