4.5 Article

Multidrug-resistant Pseudomonas aeruginosa outbreaks in two hospitals: association with contaminated hospital waste-water systems

期刊

JOURNAL OF HOSPITAL INFECTION
卷 82, 期 1, 页码 19-24

出版社

W B SAUNDERS CO LTD
DOI: 10.1016/j.jhin.2012.06.007

关键词

Pseudomonas aeruginosa; Environmental contamination; Metallo-beta-lactamase; Multidrug resistance; Nosocomial infection; Waste-water system

向作者/读者索取更多资源

Background: Multidrug-resistant Pseudomonas aeruginosa (MDR-P) expressing VIM-metallo-beta-lactamase is an emerging infection control problem. The source of many such infections is unclear, though there are reports of hospital outbreaks of P. aeruginosa related to environmental contamination, including tap water. Aim: We describe two outbreaks of MDR-P, sensitive only to colistin, in order to highlight the potential for hospital waste-water systems to harbour this organism. Methods: The outbreaks were investigated by a combination of descriptive epidemiology, inspection and microbiological sampling of the environment, and molecular strain typing. Findings: The outbreaks occurred in two English hospitals; each involved a distinct genotype of MDR-P. One outbreak was hospital-wide, involving 85 patients, and the other was limited to four cases in one specialized medical unit. Extensive environmental sampling in each outbreak yielded MDR-P only from the waste-water systems. Inspection of the environment and estates records revealed many factors that may have contributed to contamination of clinical areas, including faulty sink, shower and toilet design, clean items stored near sluices, and frequent blockages and leaks from waste pipes. Blockages were due to paper towels, patient wipes, or improper use of bedpan macerators. Control measures included replacing sinks and toilets with easier-to-clean models less prone to splashback, educating staff to reduce blockages and inappropriate storage, reviewing cleaning protocols, and reducing shower flow rates to reduce flooding. These measures were followed by significant reductions in cases. Conclusion: The outbreaks highlight the potential of hospital waste systems to act as a reservoir of MDR-P and other nosocomial pathogens. (C) 2012 The Healthcare Infection Society. Published by Elsevier Ltd. All rights reserved.

作者

我是这篇论文的作者
点击您的名字以认领此论文并将其添加到您的个人资料中。

评论

主要评分

4.5
评分不足

次要评分

新颖性
-
重要性
-
科学严谨性
-
评价这篇论文

推荐

暂无数据
暂无数据