4.7 Article

Experimental research of heat transfer performance on natural draft counter flow wet cooling tower under cross-wind conditions

期刊

INTERNATIONAL JOURNAL OF THERMAL SCIENCES
卷 47, 期 7, 页码 935-941

出版社

ELSEVIER FRANCE-EDITIONS SCIENTIFIQUES MEDICALES ELSEVIER
DOI: 10.1016/j.ijthermalsci.2007.07.010

关键词

cross wind; cooling tower; heat transfer performance; coefficient of efficiency; temperature difference; correlative equations

向作者/读者索取更多资源

The experiment in terms of heat transfer performance of natural draft counter-flow wet cooling is done for cases with cross-wind conditions. The variation of circulating-water temperature difference (Delta T) and cooling coefficient of efficiency (eta) with cross-wind velocity, circulating water inlet temperature and flow rate, are shown under cross-wind conditions, compared with cases without wind. According to experimental results, it is found that Delta T and eta are influenced by the cross-wind, and Delta T and eta can decrease mostly by 6% and 5%, respectively. When the critical Fr-l number is less than 0.174, Delta T and eta decrease with increasing cross-wind velocity, however, when it is greater than 0.174, Delta T and eta increase with increasing cross-wind velocity. In addition, based on the data regression analysis, the correlation between Delta T, eta and parameters, such as circulating-water inlet temperature and flow rate, is derived for cases with windless conditions. Furthermore, its correspondence is given out for cases with cross-wind conditions. (C) 2007 Elsevier Masson SAS. All rights reserved.

作者

我是这篇论文的作者
点击您的名字以认领此论文并将其添加到您的个人资料中。

评论

主要评分

4.7
评分不足

次要评分

新颖性
-
重要性
-
科学严谨性
-
评价这篇论文

推荐

暂无数据
暂无数据