4.5 Article

Experimental investigation on energy and exergy performance of adsorption cold storage for space cooling application

出版社

ELSEVIER SCI LTD
DOI: 10.1016/j.ijrefrig.2014.05.013

关键词

Thermal energy storage; Adsorption; Exergy; Fin-coated heat exchanger; Energy storage density; Efficiency

资金

  1. Oak Ridge National Laboratory
  2. Alternative Cooling Technologies and Applications Consortium at the Center for Environmental Energy Engineering (CEEE) at the University of Maryland, College Park

向作者/读者索取更多资源

The adsorption cold thermal energy storage (TES) system was investigated for space cooling application by considering both energy and exergy analysis. With regeneration temperature of 70 degrees C, ambient temperature of 30 degrees C, heat transfer fluid (HTF) inlet temperature for evaporator 30 degrees C, the cold energy storage density (ESD) achieved was approximately 400 kJ kg(-1) with energy efficiency of 44.6%. In addition, the exergy efficiency was 4.5%, and the loading difference was 0.165 (adsorbate/adsorbent). As the HTF mass flow rate of the evaporator was decreased, the evaporator HTF outlet temperature decreased, and the exergy efficiency increased. As the evaporator HTF inlet temperature and the regeneration temperature were increased, the cold ESD, cold thermal efficiency and cold exergy destruction all increased. As the adsorption HTF inlet temperature was decreased, the cold ESD, and recovered exergy increased. The evaporator chamber HTF inlet temperature affected more on energy and exergy performances than that of the evaporator chamber HTF mass flow rate. (C) 2014 Elsevier Ltd and IIR. All rights reserved.

作者

我是这篇论文的作者
点击您的名字以认领此论文并将其添加到您的个人资料中。

评论

主要评分

4.5
评分不足

次要评分

新颖性
-
重要性
-
科学严谨性
-
评价这篇论文

推荐

暂无数据
暂无数据