4.5 Article

Performance comparison between a single-stage and a cascade multi-functional heat pump for both air heating and hot water supply

出版社

ELSEVIER SCI LTD
DOI: 10.1016/j.ijrefrig.2013.03.003

关键词

Heat pump; Hot water; Heat exchanger; R134a; R410A; Optimization

资金

  1. Korea Institute of Energy Technology Evaluation and Planning [2010T100200474]
  2. Human Resources Development program of the KETEP [20124010203250]
  3. Korea Government Ministry of Knowledge Economy

向作者/读者索取更多资源

Multi heat pumps have been widely used in buildings due to their higher energy efficiency. Recently, demands for multi-functional heat pumps, which can provide heating, cooling, and water heating in a building, have been increased. In this study, a cascade multi-functional heat pump, combining a multi heat pump using R410A for air heating with a water heating unit using R134a for hot water supply, was investigated experimentally. The performance of the cascade multi-functional heat pump was measured by varying the refrigerant charge amount, EEV opening, water flow rate, and water inlet temperature. Test results were compared with those of a single-stage multi-functional heat pump using R410A for air and water heating. The cascade multi-functional heat pump adopting the water heating unit showed more stable air and water heating operations and higher water outlet temperatures than the single-stage multi-functional heat pump. (C) 2013 Elsevier Ltd and IIR. All rights reserved.