4.5 Article

Performance enhancement of CO2 air conditioner with a controllable ejector

出版社

ELSEVIER SCI LTD
DOI: 10.1016/j.ijrefrig.2012.05.005

关键词

Performance; Enhancement; Cycle; Carbon dioxide; Controllable ejector; Compressor; Variable speed; Two-phase flow

向作者/读者索取更多资源

This study presents performance enhancement of a transcritical CO2 air conditioner with a controllable ejector at variable operating conditions and variable compressor frequencies. The effects of ejector geometries, operating conditions and compressor frequency on the performance of an ejector expansion transcritical CO2 air conditioner were investigated. Experimental results show that the COP of a CO2 air conditioning system can be enhanced by using an ejector expansion device to replace a conventional expansion valve. This enhancement became more significant as the outdoor air temperature increased (COP increased by up to 36%), the compressor frequency decreased (COP increased by up to 147% compared to conventional cycle with compressor frequency at 50 Hz), and the motive nozzle throat diameter decreased (COP increased by up to 60%). In addition, the COP reached a maximum when the distance between motive nozzle exit and mixing section entrance was three times the mixing section diameter. (C) 2012 Elsevier Ltd and IIR. All rights reserved.

作者

我是这篇论文的作者
点击您的名字以认领此论文并将其添加到您的个人资料中。

评论

主要评分

4.5
评分不足

次要评分

新颖性
-
重要性
-
科学严谨性
-
评价这篇论文

推荐

暂无数据
暂无数据