INTERNATIONAL JOURNAL OF HEAT AND MASS TRANSFER
卷 65, 期 -, 页码 173-179出版社
PERGAMON-ELSEVIER SCIENCE LTD
DOI: 10.1016/j.ijheatmasstransfer.2013.05.069
关键词
Regenerative evaporative cooler; Cooling effectiveness; Performance test; Evaporative water flow rate
资金
- Converging Research Center Program through the National Research Foundation of Korea
- Ministry of Education, Science and Technology [2012K001376]
A regenerative evaporative cooler has been fabricated and tested for the performance evaluation. The regenerative evaporative cooler is a kind of the indirect evaporative cooler comprised of multiple pairs of dry and wet channels. The air flowing through the dry channels is cooled without any change in the humidity and at the outlet of the dry channel a part of air is redirected to the wet channel where the evaporative cooling takes place. The regenerative evaporative cooler fabricated in this study consists of the multiple pairs of finned channels in counter flow arrangement. The fins and heat transfer plates were made of aluminum and brazed for good thermal connection. Thin porous layer coating was applied to the internal surface of the wet channel to improve surface wettability. The regenerative evaporative cooler was placed in a climate chamber and tested at various operation condition. The cooling performance is found greatly influenced by the evaporative water flow rate. To improve the cooling performance, the evaporative water flow rate needs to be minimized as far as the even distribution of the evaporative water is secured. At the inlet condition of 32 degrees C and 50% RI-I, the outlet temperature was measured at 22 degrees C which is well below the inlet wet-bulb temperature of 23.7 degrees C. (C) 2013 Elsevier Ltd. All rights reserved.
作者
我是这篇论文的作者
点击您的名字以认领此论文并将其添加到您的个人资料中。
推荐
暂无数据