4.7 Article

Heat transfer and fluid flow in shrouded pin fin arrays with and without tip clearance

期刊

INTERNATIONAL JOURNAL OF HEAT AND MASS TRANSFER
卷 52, 期 25-26, 页码 5978-5989

出版社

PERGAMON-ELSEVIER SCIENCE LTD
DOI: 10.1016/j.ijheatmasstransfer.2009.08.005

关键词

Pin fin; Liquid cooling; Tip clearance; Liquid crystal; Heat transfer

向作者/读者索取更多资源

Shrouded pin fin arrays with tip clearances (Cg) up to 25% of pin height were experimentally evaluated. Pressure loss was measured (2 x 10(2) < Re(D) < 2 x 10(4)) and liquid crystal thermography was employed to obtain temperature distributions from which the impact of Cg on the mean heat transfer rate was determined for 2 x 10(2) < Re(D) < 1 x 10(4). Cg was found to influence pressure drop performance to the greatest extent at low Re(D), (<5 x 10(3)), with the effect being significantly diminished by Re(D) = 1.5 x 10(4). On a per unit pumping power basis, higher heat transfer rates were observed for dimensionless clearances (Cg/D) less than 0.2 as compared to the non-clearance case. (C) 2009 Elsevier Ltd. All rights reserved.

作者

我是这篇论文的作者
点击您的名字以认领此论文并将其添加到您的个人资料中。

评论

主要评分

4.7
评分不足

次要评分

新颖性
-
重要性
-
科学严谨性
-
评价这篇论文

推荐

暂无数据
暂无数据