INTERNATIONAL COMMUNICATIONS IN HEAT AND MASS TRANSFER
卷 38, 期 8, 页码 1086-1092出版社
PERGAMON-ELSEVIER SCIENCE LTD
DOI: 10.1016/j.icheatmasstransfer.2011.05.011
关键词
Reheat two-stage chiller; COP; Adsorption cycle; Silica gel/water
This paper deals with the performance investigation of a silica gel/water based on two-stage, four-bed adsorption chiller with different mass allocation between upper and lower beds employing the re-heat scheme. The innovative chiller is powered by waste heat or renewable energy source of temperature between 50 degrees C and 90 degrees C with a coolant of inlet temperature 30 degrees C for air conditioning purpose. The performance of the four-bed adsorption chiller employing the re-heat scheme is compared with that of the two-stage conventional chiller with the re-heat scheme using equal mass allocation. Results show that cooling capacity can be improved with the optimum allocation of adsorbent mass to the upper beds than that of lower beds. Besides, it is observed that the cooling capacity can be improved up to 10.78% while the cooling water temperature is at 20 degrees C. (C) 2011 Elsevier Ltd. All rights reserved.