4.5 Article

Air ion behavior in ventilated rooms

期刊

INDOOR AND BUILT ENVIRONMENT
卷 17, 期 2, 页码 173-182

出版社

SAGE PUBLICATIONS LTD
DOI: 10.1177/1420326X08089622

关键词

negative; air ionizer; ventilation; electrical deposition; indoor air

向作者/读者索取更多资源

Air ionizers have seen increasing use as devices for improving indoor air quality, including applications designed to reduce the transmission of infection in healthcare environments. However, little attention has been given to understanding and quantifying the physical behavior of ions in indoor air. This study presents experimental data and a theoretical model to examine the factors that influence the concentration of ions in a ventilated room. The results demonstrate how, with an ionizer in operation, the ion concentration is governed by ion-ion interactions and electrical deposition at the walls, with the ventilation rate having a minimal influence. The results also demonstrate that an ion concentration > 10(10) ions.m(-3) is necessary for these electrical effects to be significant, which has implications for the suitability of an ionizer for a particular location.

作者

我是这篇论文的作者
点击您的名字以认领此论文并将其添加到您的个人资料中。

评论

主要评分

4.5
评分不足

次要评分

新颖性
-
重要性
-
科学严谨性
-
评价这篇论文

推荐

暂无数据
暂无数据