4.6 Article

Disinfection efficacy of ultraviolet germicidal irradiation on airborne bacteria in ventilation ducts

期刊

INDOOR AIR
卷 28, 期 6, 页码 806-817

出版社

WILEY
DOI: 10.1111/ina.12504

关键词

air disinfection; bacteria susceptibility; indoor air quality; in-duct UVGI; irradiance; UV dose

资金

  1. Research Grants Council, University Grants Committee [11210015]
  2. Natural Science Foundation of Guangdong Province Education Department, China [2015KQNCX055]

向作者/读者索取更多资源

A full-scale ventilation duct ultraviolet germicidal irradiation (in-duct UVGI) system was designed to investigate its disinfection efficacy on five airborne pathogens: Serratia marcescens, Pseudomonas alcaligenes, Escherichia coli, Salmonella enterica, and Staphylococcus epidermidis, with airflow Reynolds numbers from 4 x 10(4) to 8 x 10(4). By varying the UV intensity, the susceptibility constants (Z-values) of the bacteria were experimentally determined to be 1.2, 1.0, 0.60, 0.39, and 0.37 m(2)/J for S.marcescens, P.alcaligenes, E.coli, S.enterica, and S.epidermidis, respectively. The disinfection efficacy was numerically investigated on the basis of the predicted irradiance, which included emissive irradiance and diffuse refection irradiance. The results suggest that it is vital to properly evaluate the UV dose (irradiance intensity) received by airborne bacteria to determine their Z-values. In-duct UVGI inactivated nearly all of the test bacteria with Reynolds numbers of 4 x 10(4) (inlet velocity = 3 m/s), and the disinfection efficacy decreased as Reynolds numbers increased. The in-duct UVGI system would potentially provide a supplementary solution for improving indoor air quality (IAQ) within mechanical ventilated/air-conditioned environment.

作者

我是这篇论文的作者
点击您的名字以认领此论文并将其添加到您的个人资料中。

评论

主要评分

4.6
评分不足

次要评分

新颖性
-
重要性
-
科学严谨性
-
评价这篇论文

推荐

暂无数据
暂无数据