4.6 Article

Protected zone ventilation and reduced personal exposure to airborne cross-infection

期刊

INDOOR AIR
卷 25, 期 3, 页码 307-319

出版社

WILEY
DOI: 10.1111/ina.12142

关键词

Protected zone ventilation; Cross-infection; Air velocity; Indoor contaminants; Exposure; Plane jet

资金

  1. Academy of Finland
  2. VTT Technical Research Centre of Finland [259678]
  3. Academy of Finland (AKA) [259678, 259678] Funding Source: Academy of Finland (AKA)

向作者/读者索取更多资源

The main objective of this study was to examine the performance of protected zone ventilation (PZV) and hybrid protected zone ventilation (HPZV) to reduce the direct exposure to exhaled air from others' breathing. Experimental measurements are carried out to test the performance of PZV in a full-scale office room with two breathing thermal manikins. The measurements were performed under three configurations, including two standing manikins at different distances: 0.35, 0.5, and 1.1m. When the supply air velocity is increased to 4m/s in the downward plane jet, the dimensionless concentration is 40% lower than for fully mixed ventilation, which can be considered as a measure of protection from the zoning condition. The measurement results showed that in both the PZV and the HPZV system it is possible to decrease the transmission of tracer gas from one manikin to the opposite manikin; therefore, it probably would reduce the risk of air borne cross-infection between two people at the same relative positions. The results suggest that PZV and HPZV may be used to reduce the exposure of people in a protected zone from indoor pollutants emitted in a source zone.

作者

我是这篇论文的作者
点击您的名字以认领此论文并将其添加到您的个人资料中。

评论

主要评分

4.6
评分不足

次要评分

新颖性
-
重要性
-
科学严谨性
-
评价这篇论文

推荐

暂无数据
暂无数据