Distributed generation; distribution relaying; renewable energy
Due to the variety of distribution generation (DG) sizes and technologies connecting to distribution networks, and the concerns associated with out-of phase reclosing, anti-islanding continues to be an issue where no clear solution exists. This paper presents an autoground approach that was proposed in the context of an IEEE working group on best practices for DG protection. A prototype system was constructed using standard distribution apparatus and a recloser controller, and it was tested on the utility's distribution test line. Results show that the anti-islanding detection time is approximately a cycle longer than the delay associated with application of the autoground. Once the autoground was applied, the DG was disconnected within 1 cycle on overcurrent protection. The solution is inherently scalable, applicable to all DG types, is configurable to various reclosing practices and does not require additional equipment or settings changes at the producer's site.