Application of Wide Area Measurement Systems to Islanding Detection of Bulk Power Systems

期刊

IEEE TRANSACTIONS ON POWER SYSTEMS
卷 28, 期 2, 页码 2006-2015

出版社

IEEE-INST ELECTRICAL ELECTRONICS ENGINEERS INC
DOI: 10.1109/TPWRS.2013.2250531

关键词

Event detection; frequency disturbance recorder; islanding detection; phasor measurement unit; wide area measurement system

资金

  1. NSF
  2. Midwest ISO
  3. National Natural Science Foundation of China [51007080]

向作者/读者索取更多资源

A fast islanding detection tool can help power dispatchers monitor and control power system operations. Frequency monitoring network (FNET) is a low cost and quickly deployable wide-area phasor measurement system at the distribution system level. The frequency disturbance recorder (FDR) in FNET is actually a single-phase phasor measurement unit (PMU) installed at ordinary 120 V outlets in the sense that it measures the voltage phase angle, amplitude, and frequency from a single-phase voltage source. Based on the data collected by the FDRs deployed in the North American power grid, two islanding detection methods, the frequency difference method and the change of angle difference method, are proposed. The nine real cases recorded, including islanding cases, generation trip cases, load shedding cases and oscillation cases, are presented to verify the proposed methods of islanding detection. Sensitivity analysis on the thresholds of the frequency deviation and angle deviation is done based on the real-measurement data for obtaining the insensitive interval of two thresholds. The results show that the proposed methods can correctly detect power system islanding, and will not be falsely triggered by generation trips, load shedding and system oscillations.

作者

我是这篇论文的作者
点击您的名字以认领此论文并将其添加到您的个人资料中。

评论

主要评分

4.7
评分不足

次要评分

新颖性
-
重要性
-
科学严谨性
-
评价这篇论文

推荐

暂无数据
暂无数据