Support Vector Machine-Based Algorithm for Post-Fault Transient Stability Status Prediction Using Synchronized Measurements

期刊

IEEE TRANSACTIONS ON POWER SYSTEMS
卷 26, 期 3, 页码 1474-1483

出版社

IEEE-INST ELECTRICAL ELECTRONICS ENGINEERS INC
DOI: 10.1109/TPWRS.2010.2082575

关键词

Nonlinear classifiers; phasor measurement units; support vector machines; transient stability; wide area protection and control

资金

  1. Manitoba Hydro, Winnipeg, MB, Canada
  2. Electrificacion del Caroni (EDELCA), Venezuela

向作者/读者索取更多资源

The paper first shows that the transient stability status of a power system following a large disturbance such as a fault can be early predicted based on the measured post-fault values of the generator voltages, speeds, or rotor angles. Synchronously sampled values provided by phasor measurement units (PMUs) of the generator voltages, frequencies, or rotor angles collected immediately after clearing a fault are used as inputs to a support vector machines (SVM) classifier which predicts the transient stability status. Studies with the New England 39-bus test system and the Venezuelan power network indicated that faster and more accurate predictions can be made by using the post-fault recovery voltage magnitude measurements as inputs. The accuracy and robustness of the transient stability prediction algorithm with the voltage magnitude measurements was extensively tested under both balanced and unbalanced fault conditions, as well as under different operating conditions, presence of measurement errors, voltage sensitive loads, and changes in the network topology. During the various tests carried out using the New England 39-bus test system, the proposed algorithm could always predict when the power system is approaching a transient instability with over 95% success rate.

作者

我是这篇论文的作者
点击您的名字以认领此论文并将其添加到您的个人资料中。

评论

主要评分

4.7
评分不足

次要评分

新颖性
-
重要性
-
科学严谨性
-
评价这篇论文

推荐

暂无数据
暂无数据