4.7 Article

Generator Coherency Using the Hilbert-Huang Transform

期刊

IEEE TRANSACTIONS ON POWER SYSTEMS
卷 23, 期 4, 页码 1701-1708

出版社

IEEE-INST ELECTRICAL ELECTRONICS ENGINEERS INC
DOI: 10.1109/TPWRS.2008.2004736

关键词

Empirical mode decomposition; generator coherency; Hilbert-Huang transform; intrinsic mode function; proper orthogonal decomposition; wide-area measurement system

资金

  1. Industrial Research and Development unit of IIT-Delhil [M100056]

向作者/读者索取更多资源

Coherency between generators is tracked, by examining the instantaneous phase differences among interarea oscillations and swing curves in disturbed multiarea power systems. Huang's empirical mode decomposition is applied to extract dominant oscillatory modes from interarea oscillations/swing curves. Hilbert transform on these modes yields their instantaneous phase. The coherency is thus revealed by the temporal evolution of the phase difference among interarea oscillations/generator swing curves. The technique is illustrated using simulations on a test system, as well as actual wide-area measurements.

作者

我是这篇论文的作者
点击您的名字以认领此论文并将其添加到您的个人资料中。

评论

主要评分

4.7
评分不足

次要评分

新颖性
-
重要性
-
科学严谨性
-
评价这篇论文

推荐

暂无数据
暂无数据