4.8 Article

Modeling and Analysis of Grid Harmonic Distortion Impact of Aggregated DG Inverters

期刊

IEEE TRANSACTIONS ON POWER ELECTRONICS
卷 26, 期 3, 页码 786-797

出版社

IEEE-INST ELECTRICAL ELECTRONICS ENGINEERS INC
DOI: 10.1109/TPEL.2010.2091286

关键词

Distributed generation (DG); distortion; harmonic interactions; inverters; modeling

向作者/读者索取更多资源

This paper proposes an impedance-based analytical method for modeling and analysis of harmonic interactions between the grid and aggregated distributed generation (DG) inverters. The root cause of harmonic interaction/resonance problems is the impedance-network quasi-resonance between the effective output impedance of the inverter and the equivalent grid impedance at the connection point. Starting with the output impedance modeling of an inverter, a Norton model of the inverter is derived. Comparing with the switching model and the average model of the inverter, simulation results show the effectiveness of the model. This paper proposes that impedance limits should be specified and used as an extra design constraint for DG inverters in order to minimize the harmonic distortion impact on the grid. Assuming the impedance models of individual inverters and local loads within a distribution grid are known, especially in the case of new grids under construction, harmonic interactions between the grid and a certain number of DG inverters can be preliminarily estimated.

作者

我是这篇论文的作者
点击您的名字以认领此论文并将其添加到您的个人资料中。

评论

主要评分

4.8
评分不足

次要评分

新颖性
-
重要性
-
科学严谨性
-
评价这篇论文

推荐

暂无数据
暂无数据