Transmission-Line Fault Analysis Using Synchronized Sampling

期刊

IEEE TRANSACTIONS ON POWER DELIVERY
卷 29, 期 2, 页码 942-950

出版社

IEEE-INST ELECTRICAL ELECTRONICS ENGINEERS INC
DOI: 10.1109/TPWRD.2013.2296788

关键词

Electromagnetic transients; fault detection; fault location; power system faults; power system protection

资金

  1. ARPA-E under GENI contract [0473-1510]

向作者/读者索取更多资源

An automated analysis approach, which can automatically characterize fault and subsequent relay operation, is the focus of this paper. It utilizes synchronized samples captured during transients from both ends of the transmission line to detect, classify, and locate transmission-line faults and can verify that the tripped line has indeed experienced a fault. The proposed method is tested for several faults simulated on an IEEE 118-bus test system and it has been concluded that it can detect and classify a fault using prefault and postfault recorded samples within 7 ms of fault inception and can accurately locate a fault with 3% accuracy. This time response performance is highly desirable since with the increasing use of modern circuit breakers, which can open the faulty line in less than two cycles, the time window of the captured waveforms is significantly reduced due to the unavailability of measurement signals after breakers open.