4.6 Article

Measuring Paper Water Content of Transformers: A New Approach Using Cellulose Isotherms in Nonequilibrium Conditions

期刊

IEEE TRANSACTIONS ON POWER DELIVERY
卷 28, 期 3, 页码 1433-1439

出版社

IEEE-INST ELECTRICAL ELECTRONICS ENGINEERS INC
DOI: 10.1109/TPWRD.2013.2248396

关键词

Moisture measurement; oil insulation; paper insulation; power transformer insulation; power transformers

资金

  1. Ausgrid
  2. Citipower/powercor
  3. Cooper Power Systems
  4. Dynamic Ratings
  5. Energex
  6. Ergon Energy
  7. FM Global
  8. Powerlink Queensland
  9. TJ\H2b Analytical Services
  10. Transgrid
  11. Transpower New Zealand
  12. UK PowerNetworks
  13. Wilson Transformer Company

向作者/读者索取更多资源

In this paper, we discuss a better method to measure the paper water content of transformers using cellulose isotherms. The advantage of the new method is that the transformer oil and cellulosic insulation do not need to be in thermodynamic equilibrium. Instead, the temperature needs to be cycling in order to determine when the direction of water migration, whether out of or into the oil changes. The reversal in water migration can be used to determine the vapor pressure of the water adsorbed by the cellulose. This method was tested using 12 different conditions similar to those within a normally operating transformer. The results showed close agreement when this method is used. The significance is that isotherm equations can now be used even when insulation media are not in equilibrium.

作者

我是这篇论文的作者
点击您的名字以认领此论文并将其添加到您的个人资料中。

评论

主要评分

4.6
评分不足

次要评分

新颖性
-
重要性
-
科学严谨性
-
评价这篇论文

推荐

暂无数据
暂无数据