4.6 Article

Analysis of Dual-Infeed HVDC With LCC-HVDC and VSC-HVDC

期刊

IEEE TRANSACTIONS ON POWER DELIVERY
卷 27, 期 3, 页码 1529-1537

出版社

IEEE-INST ELECTRICAL ELECTRONICS ENGINEERS INC
DOI: 10.1109/TPWRD.2012.2189139

关键词

Apparent increase in short circuit ratio (AISCR); commutation failure immunity index (CFII); dual-infeed HVDC; line-commutated converter; maximum available power; temporary overvoltage; voltage-source converter (VSC)

资金

  1. innovation talent cultivation Program of 211 Project for North China Electric Power University (the 3rd phase)
  2. Industrial Research Chair Program of Natural Sciences and Engineering Research Council of Canada (NSERC)
  3. National Science Foundation of China [51177042]

向作者/读者索取更多资源

The impact of a voltage source converter-based HVDC (VSC-HVDC) infeed on a line-commutated converter-based HVDC infeed (LCC-HVDC) at the same busbar is investigated. Steady-state aspects such as the maximum available power (MAP) as well as transient aspects such as temporary overvoltage (TOV) and commutation failure immunity index are considered in the analysis. The results show that VSC-HVDC improves the maximum available power, reduces TOV, and makes the LCC-HVDC less susceptible to commutation failure. The resulting improvement in performance of the LCC-HVDC is quantified by a proposed apparent increase in short circuit ratio (AISCR) index. AISCR is a measure of the increase in short-circuit ratio for the LCC-HVDC that would be necessary in the absence of the VSC-HVDC link to obtain similar performance. The analytical results are validated by a detailed electromagnetic transient simulation.

作者

我是这篇论文的作者
点击您的名字以认领此论文并将其添加到您的个人资料中。