4.6 Article

Path Characteristic Frequency-Based Fault Locating in Radial Distribution Systems Using Wavelets and Neural Networks

期刊

IEEE TRANSACTIONS ON POWER DELIVERY
卷 26, 期 2, 页码 772-781

出版社

IEEE-INST ELECTRICAL ELECTRONICS ENGINEERS INC
DOI: 10.1109/TPWRD.2010.2050218

关键词

Artificial neural network; fault location; path characteristic frequency; wavelet transform

向作者/读者索取更多资源

This paper proposes a new algorithm for localizing phase to ground faults in an electric power distribution system. Fault-originated traveling waves propagate along the distribution paths in both directions away from the fault point and are reflected at line terminations, junctions between feeders, laterals, and the fault location. Depending on the paths which traveling waves reciprocate through, the transient signal at each node contains certain path characteristic frequencies (PCFs). Energy spectrum of the transient signal has high density around the path characteristic frequencies. On this basis, the transient voltage is decomposed by a wavelet filter and its energy spectrum is decomposed into different levels. Depending on the bandwidth of the wavelet filter and the path characteristic frequencies, the decomposed signal in each level contains a certain percentage of energy. Then, a neural network-based methodology is proposed as a power distribution line fault locator. Energy percentage in each level is the candidate feature for training the artificial neural network. Simulations and the training process for the neural network are performed respectively using ATP/EMTP and MATLAB. It is shown that the results of the proposed algorithm are quite satisfactory.

作者

我是这篇论文的作者
点击您的名字以认领此论文并将其添加到您的个人资料中。

评论

主要评分

4.6
评分不足

次要评分

新颖性
-
重要性
-
科学严谨性
-
评价这篇论文

推荐

暂无数据
暂无数据