4.6 Article

Damping Performance Analysis of IPFC and UPFC Controllers Using Validated Small-Signal Models

期刊

IEEE TRANSACTIONS ON POWER DELIVERY
卷 26, 期 1, 页码 446-454

出版社

IEEE-INST ELECTRICAL ELECTRONICS ENGINEERS INC
DOI: 10.1109/TPWRD.2010.2060371

关键词

Decoupled control; electromagnetic transients (EMT); flexible ac transmission system (FACTS); interline power-flow controller (IPFC); small-signal stability; unified power-flow controller (UPFC)

资金

  1. Natural Sciences and Engineering Research Council of Canada (NSERC)

向作者/读者索取更多资源

The paper discusses the dynamic behavior of two different flexible ac transmission system devices; the interline power-flow controller (IPFC) and the unified power-flow controller (UPFC) in a benchmark system. The small-signal model of the interline power-flow controller is developed and validated using detailed electromagnetic transients simulation. Using this validated model, the damping capabilities of the IPFC and the UPFC are compared and rationalized. From a small-signal dynamics point of view, it is shown that the series branches of these devices essentially segment the network creating a new structure. This structure change may be used to effectively improve system damping without requiring the design of a tuned feedback controller. The IPFCs two series branches in contrast to the UPFC's single series branch permit more opportunities for network segmentation. Hence, the IPFC has greater potential for improving the system's dynamic performance.

作者

我是这篇论文的作者
点击您的名字以认领此论文并将其添加到您的个人资料中。

评论

主要评分

4.6
评分不足

次要评分

新颖性
-
重要性
-
科学严谨性
-
评价这篇论文

推荐

暂无数据
暂无数据