IEEE TRANSACTIONS ON POWER DELIVERY
卷 26, 期 2, 页码 954-962出版社
IEEE-INST ELECTRICAL ELECTRONICS ENGINEERS INC
DOI: 10.1109/TPWRD.2010.2084111
关键词
Controlled switching; electromagnetic transients; switching overvoltages; three-phase reclosing; transmission lines
资金
- National Council for Scientific and Technological Development (CNPq)
- CAPES
- FAPESP, Brazil
- NSERC, Canada
This paper proposes a new control method to reduce overvoltages due to three-phase reclosing for shunt compensated transmission lines (TL). The method detects the first minimum voltage region of the beating across the circuit breakers after protection dead time and works independently of voltage zero crossing, reducing significantly the reclosure time. The controller was tested on a Real Time Digital Simulator (RTDS) and its performance was compared to the traditional preinsertion resistor approach and another existing control method.