4.6 Article

Experimental Investigation to Calculate the Lightning Outage Rate of a Distribution System

期刊

IEEE TRANSACTIONS ON POWER DELIVERY
卷 25, 期 4, 页码 2913-2922

出版社

IEEE-INST ELECTRICAL ELECTRONICS ENGINEERS INC
DOI: 10.1109/TPWRD.2010.2053563

关键词

Analysis model; direct lightning stroke; distribution line; fault; indirect lightning stroke; lightning

资金

  1. Distribution Department of Tokyo Electric Power Co.

向作者/读者索取更多资源

A method was devised for estimating the lightning outage rate in distribution lines based on a field study. The observation has pointed out that direct lightning flashes to distribution systems were the main cause of line outages; however, a greater number of arresters reduced the number of distribution line faults due to direct lightning strokes. The observation also suggested that the number of direct lightning strike flashovers changes by two factors: 1) the installation rate of surge arresters and 2) the density of the lines. It is noted that this assumption can be applied to the distribution system that has a greater number of transformer-containing arresters. Based on these factors, a computer program was proposed to estimate the lightning outage rate due to lightning strokes, and the calculated results showed good agreement with the observed values in the actual lines. These results suggest that this method can contribute to the evaluation of lightning protection devices, and can lead to effective lightning protection practices.

作者

我是这篇论文的作者
点击您的名字以认领此论文并将其添加到您的个人资料中。

评论

主要评分

4.6
评分不足

次要评分

新颖性
-
重要性
-
科学严谨性
-
评价这篇论文

推荐

暂无数据
暂无数据