4.7 Article

Development and Application of High-Frequency Sensor for Corona Current Measurement under Ultra High-Voltage Direct-Current Environment

期刊

出版社

IEEE-INST ELECTRICAL ELECTRONICS ENGINEERS INC
DOI: 10.1109/TIM.2011.2179337

关键词

Corona current; electric field; finite-element method (FEM); high-frequency sensor; high-voltage direct-current (HVDC)

资金

  1. National Program on Key Basic Research Project (973 Program) [2011CB209402]
  2. State Grid Corporation of Science and Technology Program [GY71-11-024]

向作者/读者索取更多资源

Corona current measurement is essential for research into corona discharge under ultra high-voltage direct-current (HVDC) environment. The sensor is extremely important due to the small (microampere) amplitude of the corona current and the wide (dc to tens of megahertz) range in frequency. In this paper, a high-frequency sensor is described, and its application is introduced for accurate measurement of corona current under HVDC environment. Based on the finite-element method and the charge simulation method, the structure of the sensor is determined considering a +/- 1200-kV environment. The sensor is immune to the effects from the external environments such as vibration and temperature changes. Results indicate that the sensor is feasible for corona current measurement.

作者

我是这篇论文的作者
点击您的名字以认领此论文并将其添加到您的个人资料中。

评论

主要评分

4.7
评分不足

次要评分

新颖性
-
重要性
-
科学严谨性
-
评价这篇论文

推荐

暂无数据
暂无数据