Strong and Weak Electric Field Interfering: Capacitive Icing Detection and Capacitive Energy Harvesting on a 220-kV High-Voltage Overhead Power Line

期刊

IEEE TRANSACTIONS ON INDUSTRIAL ELECTRONICS
卷 58, 期 7, 页码 2597-2604

出版社

IEEE-INST ELECTRICAL ELECTRONICS ENGINEERS INC
DOI: 10.1109/TIE.2010.2098362

关键词

Capacitance measurement; decoupling of systems; energy harvesting; galvanic isolator; high-voltage overhead power line; icing detection; online condition monitoring; optical coupler; power system reliability; wireless communication

向作者/读者索取更多资源

This paper focuses on problems which arise when both a power-harvesting system based on a capacitive principle and a capacitive measurement device [i.e., a capacitance-to-digital converter (CDC)] are used in one electronic system to build up an autonomous measurement device for icing detection on a high-voltage overhead power line. The overall capacitance of the measurement circuitry between the conductor and the energy harvester shell must remain within a well-defined range to keep the energy-harvesting circuitry operational and to operate the CDC within its specifications. A decoupling solution for both the data path and the power supply unit has been implemented and verified experimentally in a high-voltage laboratory and a field test.