期刊
IEEE TRANSACTIONS ON ELECTROMAGNETIC COMPATIBILITY
卷 56, 期 3, 页码 668-674出版社
IEEE-INST ELECTRICAL ELECTRONICS ENGINEERS INC
DOI: 10.1109/TEMC.2014.2309146
关键词
Electromagnetic transient program; lightning flashover rates; lightning-induced overvoltage; Monte Carlo method; overhead distribution lines
This paper presents a procedure for evaluation of lightning performance of overhead distribution lines. Because both voltages from direct strokes and nearby strokes may cause flashovers in distribution lines, flashover rates due to them need to be analyzed. The procedure is implemented in electromagnetic transient program, and the Monte Carlo method is used to take into account the random nature of lightning parameters. The lightning-induced voltages are calculated with an equivalent circuit derived from Agrawal et al. formula. The influence of insulation level and spacing between surge arresters on lightning flashover rates is analyzed with the procedure. For a line with low-insulation level about 150 kV above high conductivity ground or with high-insulation level about 300 kV above low conductivity ground, the spacing between arresters is best less than 400 m. But for a line with low-insulation level above low conductivity ground, it is better to reduce the spacing to 200 m.
作者
我是这篇论文的作者
点击您的名字以认领此论文并将其添加到您的个人资料中。
推荐
暂无数据