4.2 Article

The Brazilian Experience With the Use of the Shield Wire Line Technology (SWL) for Energy Distribution

期刊

IEEE LATIN AMERICA TRANSACTIONS
卷 7, 期 6, 页码 650-656

出版社

IEEE-INST ELECTRICAL ELECTRONICS ENGINEERS INC
DOI: 10.1109/TLA.2009.5419362

关键词

lightning; power distribution; power transmission line; energized shield wire line; operational indexes

向作者/读者索取更多资源

This paper presents an analysis of the impact of the lightning overvoltages on the operational performance of the energized shield wire line technology (SWL) implemented in two locations of the State of Rondonia, Brazil. The analysis covers the periods of 1996 to 2000 (SWL Jaru) and 1997 to 2002 (SWL Itapua do Oeste), and shows that lightning is responsible for most of the system outages. The paper describes the satisfactory results achieved with the system, showing that the isolation and energization of the shield wires does not deteriorate the lightning performance of the 230 kV transmission lines. Comparisons between the performances of the SWL technology, conventional 34.5 kV lines, and thermal power plants in operation in the same region are also presented. The results demonstrate the technical and economical viability of the SWL technology and show that its application can lead to a postponement of investments.

作者