A hybrid lumped capacitance-CFD model for the simulation of data center transients

期刊

HVAC&R RESEARCH
卷 20, 期 6, 页码 688-702

出版社

TAYLOR & FRANCIS INC
DOI: 10.1080/10789669.2014.930280

关键词

-

资金

  1. IBM Corporation
  2. Syracuse Center of Excellence in Environmental and Energy Systems

向作者/读者索取更多资源

Transient thermal events in air-cooled data centers may lead to undesirable operating conditions such as the formation of hot spots and associated degradation of equipment reliability. These transients may be caused by cooling equipment failures, server load changes, or other time-dependent scenarios in data center operations. This paper introduces a fast-executing hybrid computational fluid dynamics (CFD)/Lumped-Capacitance model for predicting server inlet temperatures resulting from common transient events such as server shutdown, partial or total chilled water interruption, or partial or total failure of the computer room air handlers (CRAH). The model uses initial steady-state CFD or experimental data in combination with several lumped-capacitance models of the various thermal masses in the data center, including the servers, the room enclosure, the CRAHs and the underfloor plenum. The inclusion of these thermal capacitances and their associated thermal conductance was found to be an important contributor to the overall transient response of the data center air-space. The model predictions have been compared with experimental data obtained in a three-rack data-center test cell and found to agree well with the experimental measurements. Examples of the application of the model to more realistic data center configurations are also given.

作者

我是这篇论文的作者
点击您的名字以认领此论文并将其添加到您的个人资料中。

评论

主要评分

3.9
评分不足

次要评分

新颖性
-
重要性
-
科学严谨性
-
评价这篇论文

推荐

暂无数据
暂无数据