4.4 Article

Experimental studies on heat and mass transfer performance of a coiled tube absorber for R134a-DMAC based absorption cooling system

期刊

HEAT AND MASS TRANSFER
卷 45, 期 1, 页码 47-54

出版社

SPRINGER
DOI: 10.1007/s00231-008-0396-2

关键词

-

向作者/读者索取更多资源

Absorber is an important component in vapor absorption refrigeration system and its performance has greater influence in overall efficiency of absorption machines. Falling film heat and mass transfer in an absorber is greatly influenced by fluid properties, geometry of heat exchanger and its operating parameters. This paper presents on the results of experimental studies on the heat and mass transfer characteristics of a coiled tube falling film absorber, using 1,1,1,2-Tetrafluroethane(R-134a) and N-N Dimethyl Acetamide (DMAC) as working fluids. The effects of film Reynolds number, inlet solution temperature and cooling water temperature on absorber heat load, over all heat transfer coefficient and mass of refrigerant absorbed are presented and discussed. Normalized solution and coolant temperature profiles and refrigerant mass absorbed along the height of absorber are also observed from the experimental results. The optimum over all heat transfer coefficient for R-134a-DMAC solution found to be 726 W/m(2)K for a film Reynolds number of 350. The R-134a vapour absorption rate is maximum in the normalized coil height of 0.6 to 1.