4.7 Article

Experimental study on the thermal performance of mechanical cooling tower with rotational splash type packing

Journal

ENERGY CONVERSION AND MANAGEMENT
Volume 87, Issue -, Pages 530-538

Publisher

PERGAMON-ELSEVIER SCIENCE LTD
DOI: 10.1016/j.enconman.2014.07.036

Keywords

Wet cooling tower; Counter flow; Rotational packing; Thermal performance

Ask authors/readers for more resources

This paper deals with an experimental investigation of thermal performance of a forced draft counter flow wet cooling tower filled with a rotational splash type packing. Tower's parameters are compared when the packing has been rotated and when it does not rotate (like common existing towers). However, no references regarding the effect of the rotational packing on the cooling tower performance have been found in the reviewed bibliography. The packing has 0.85 m(2) area and consists of six horizontal wooden slats fixed on a threaded metallic shaft. This investigation is carried out for three inlet air temperatures 27 degrees C, 34 degrees C and 41 degrees C while water temperature is kept constant at 45 degrees C. The ranges of packing velocities are between 0 to 17 RPM and also several ranges of water to air flow rate ratio are experimented: 0.4

Authors

I am an author on this paper
Click your name to claim this paper and add it to your profile.

Reviews

Primary Rating

4.7
Not enough ratings

Secondary Ratings

Novelty
-
Significance
-
Scientific rigor
-
Rate this paper

Recommended

No Data Available
No Data Available