4.7 Article

Validation of EnergyPlus thermal simulation of a double skin naturally and mechanically ventilated test cell

Journal

ENERGY AND BUILDINGS
Volume 75, Issue -, Pages 511-522

Publisher

ELSEVIER SCIENCE SA
DOI: 10.1016/j.enbuild.2014.02.043

Keywords

Thermal simulation; Validation; Double skin facade; EnergyPlus; Natural ventilation; Passive house

Funding

  1. Fundacao Calouste Gulbenkian [126724]

Ask authors/readers for more resources

This paper presents a thermal simulation validation study of the typical precision that a trained thermal simulation engineer can expect to obtain for the simulation of a room connected to a naturally ventilated double skin facade. The open source building thermal simulation tool EnergyPlus is used to predict air and surface temperatures in a free running weather exposed test cell. The validation approach used does not allow for fine tuning the simulation model by trial and error and includes a sensitivity analysis on the impact of different simulation options such as: number of thermal zones, ground heat transfer and accuracy of solar radiation data. The analysis of the results is consistent with the engineering application goal by focusing on standard indicators: average error, bias and difference between predicted and measured daily maximums. The results show good agreement between simulation and experiment, with an average simulation error in air and radiant temperature of 1.4 degrees C and an average daily maximum error of 2.5 C. (C) 2014 Elsevier B.V. All rights reserved.

Authors

I am an author on this paper
Click your name to claim this paper and add it to your profile.

Reviews

Primary Rating

4.7
Not enough ratings

Secondary Ratings

Novelty
-
Significance
-
Scientific rigor
-
Rate this paper

Recommended

No Data Available
No Data Available