4.7 Article

Experimental study of a heat pump system with flash-tank coupled with scroll compressor

Journal

ENERGY AND BUILDINGS
Volume 40, Issue 5, Pages 697-701

Publisher

ELSEVIER SCIENCE SA
DOI: 10.1016/j.enbuild.2007.05.003

Keywords

heat pump; economizer; scroll compressor; flash-tank

Ask authors/readers for more resources

A heat pump system with a flash-tank coupled with a scroll compressor is compared with a system with a sub-cooler. The heat pump performance was measured experimentally. The heating capacity of the prototype decreased as the evaporation temperature decreased, but the decrease was much slower than that of a conventional air-source heat pump. The power input varied slightly with the evaporation temperature. The heat pump system with a flash-tank is more efficient than the system with a sub-cooler at low ambient temperatures, so it will be very useful as a small capacity air-source heat pump. (C) 2007 Published by Elsevier B.V.