Journal
ELECTRIC POWER COMPONENTS AND SYSTEMS
Volume 40, Issue 2, Pages 131-146Publisher
TAYLOR & FRANCIS INC
DOI: 10.1080/15325008.2011.629331
Keywords
robust control; linear quadratic Gaussian/loop transfer recovery with integral action; doubly fed induction generator; wind energy conversion system
Categories
Funding
- CNPq [620165/2008-1]
Ask authors/readers for more resources
This article presents a novel application of the multivariable robust controller linear quadratic Gaussian/loop transfer recovery with integral action to a doubly fed induction generator. Furthermore, this study investigates robustness and performance in the face of variations of internal parameters of the machine and speed. Experimental results obtained from a laboratory prototype that uses a 2-kW machine are presented to validate and demonstrate the robustness and performance of the proposed controller through the comparison with the proportional and integral controller employed in a wind energy conversion system with doubly fed induction generator machines.
Authors
I am an author on this paper
Click your name to claim this paper and add it to your profile.
Reviews
Recommended
No Data Available