4.8 Article

A technique for power supply harmonic impedance estimation using a controlled voltage disturbance

Journal

IEEE TRANSACTIONS ON POWER ELECTRONICS
Volume 17, Issue 2, Pages 207-215

Publisher

IEEE-INST ELECTRICAL ELECTRONICS ENGINEERS INC
DOI: 10.1109/63.988831

Keywords

impedance measurement; industrial power systems; power quality; power system measurements

Ask authors/readers for more resources

A method for power system impedance estimation is presented. The method employs a power converter to inject a voltage transient onto the supply system. As the technique employs controlled power electronic devices it may be used as a stand alone piece of a portable measurement equipment, or it may be embedded into the functions of an active shunt filter for improved harmonic control. The impedance is estimated through correlation of the measured voltage and current transients. Simulations and experimental results demonstrate the measurement technique is highly accurate and effective.

Authors

I am an author on this paper
Click your name to claim this paper and add it to your profile.

Reviews

Primary Rating

4.8
Not enough ratings

Secondary Ratings

Novelty
-
Significance
-
Scientific rigor
-
Rate this paper

Recommended

No Data Available
No Data Available