4.3 Article

Modelling and experimental performance analysis of solar-assisted ground source heat pump system

Publisher

TAYLOR & FRANCIS LTD
DOI: 10.1080/0952813X.2015.1056242

Keywords

Solar energy; ground source heat pump; artificial neural network; adaptive neuro-fuzzy inference system

Funding

  1. Scientific Research Projects Administration Unit of Firat University [2009/1498]

Ask authors/readers for more resources

In this study, slinky (the slinky-loop configuration is also known as the coiled loop or spiral loop of flexible plastic pipe)type ground heat exchanger (GHE) was established for a solar-assisted ground source heat pump system. System modelling is performed with the data obtained from the experiment. Artificial neural network (ANN) and adaptive neuro-fuzzy inference system (ANFIS) are used in modelling. The slinky pipes have been laid horizontally and vertically in a ditch. The system coefficient of performance (COPsys) and the heat pump coefficient of performance (COPhp) have been calculated as 2.88 and 3.55, respectively, at horizontal slinky-type GHE, while COPsys and COPhp were calculated as 2.34 and 2.91, respectively, at vertical slinky-type GHE. The obtained results showed that the ANFIS is more successful than that of ANN for forecasting performance of a solar ground source heat pump system.