4.7 Article

CFD study of exhaled droplet transmission between occupants under different ventilation strategies in a typical office room

Journal

BUILDING AND ENVIRONMENT
Volume 46, Issue 2, Pages 397-408

Publisher

PERGAMON-ELSEVIER SCIENCE LTD
DOI: 10.1016/j.buildenv.2010.08.003

Keywords

Exhaled droplets; Ventilation strategy; Aerosol transmission; Eulerian drift-flux method

Funding

  1. Research Grant Committee, Hong Kong, China [RGC GRF 526508]
  2. National Natural Science Foundation of China [50808133]
  3. Tongji University

Ask authors/readers for more resources

This paper investigated the transmission of respiratory droplets between two seated occupants equipped with one type of personalized ventilation (PV) device using round movable panel (RMP) in an office room. The office was ventilated by three different total volume (TV) ventilation strategies, i.e. mixing ventilation (MV), displacement ventilation (DV), and under-floor air distribution (UFAD) system respectively as background ventilation methods. Concentrations of particles with aerodynamic diameters of 0.8 mu m, 5 mu m, and 16 mu m as well as tracer gas were numerically studied in the Eulerian frame. Two indexes, i.e. intake fraction (IF) and concentration uniformity index R-C were introduced to evaluate the performance of ventilation systems. It was found that without PV, DV performed best concern protecting the exposed manikin from the pollutants exhaled by the polluting manikin. In MV when the exposed manikin opened RMP the inhaled air quality could always be improved. In DV and UFAD application of RMP might sometimes, depending on the personalized airflow rate, increase the exposure of the others to the exhaled droplets of tracer gas, 0.8 mu m particles, and 5 mu m particles from the infected occupants. Application of PV could reduce R-C for all the three TV systems of 0.8 mu m and 5 mu m particles. PV enhanced mixing degree of particles under DV and UFAD based conditions much stronger than under MV based ones. PV could increase the average concentration in the occupied zone of the exposed manikin as well as provide clean personalized airflow. Whether inhaled air quality could be improved depended on the balance of pros and cons of PV. (C) 2010 Elsevier Ltd. All rights reserved.

Authors

I am an author on this paper
Click your name to claim this paper and add it to your profile.

Reviews

Primary Rating

4.7
Not enough ratings

Secondary Ratings

Novelty
-
Significance
-
Scientific rigor
-
Rate this paper

Recommended

No Data Available
No Data Available